REFRIGERANT • PT DATA v1

R-416A

PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.

At a glance

SAFETY • A1
CURVE • dew
POINTS • 421
GWP
1084
ODP
0.01
Curves available
Dew + Bubble
Pressure range (psig)
-14.69 to 529.62
Temperature range (°F)
-200 to 220
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-7.7linear
2537.1linear
5063.2linear
7582.4linear
10097.9linear
150122.5linear
200142linear
250158.3linear
300172.4linear
350184.8linear
400195.9linear
450206linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-8.5exact
-20-4exact
03exact
2013.2exact
4027.3exact
6046.4exact
8071.5exact
100103.7exact
120144.2exact
140194.3exact

Data source & notes

PT asset ID
r416a
Original name
R-416A
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)
Safety note: PT lookups are a foundational building block for charging and diagnostics, but they do not replace OEM procedures or full system context.