At a glance

SAFETY • A1
CURVE • bubble
POINTS • 421
GWP
1084
ODP
0.01
Curves available
Dew + Bubble
Pressure range (psig)
-14.69 to 535.22
Temperature range (°F)
-200 to 220
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.

Quick actions

These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.

Open PT Chart
Fast lookup (pressure ↔ temp)
Open →
Browse Equipment
See equipment using this refrigerant
Open →
Superheat/Subcool
Preselect this refrigerant
Open →
Charge Calculator
Line set adjustments
Open →
Curve toggle
Tip: For blends, evaporator saturation is typically based on dew, and condenser saturation is typically based on bubble.

Pressure → Saturation temperature (quick)

Linear interpolation between nearest points. Out-of-range values show “—”.

Pressure (psig)Sat Temp (°F)Source
0-11.1linear
2533.8linear
5059.9linear
7579.2linear
10094.7linear
150119.5linear
200139.1linear
250155.6linear
300169.8linear
350182.5linear
400193.9linear
450204.2linear

Temperature → Saturation pressure (quick)

Useful for “I have a target saturation temp—what pressure should I see?” checks.

Temp (°F)Sat Pressure (psig)Source
-40-7.9exact
-20-3exact
04.5exact
2015.2exact
4030.1exact
6050.1exact
8076.2exact
100109.5exact
120151.2exact
140202.6exact

Data source & notes

PT asset ID
r416a
Original name
R-416A
CAS
Units
psig / F (atm: 14.6959 psi)
Default curve
dew
PT index version
v1(from /assets/pt/v1/index.json)