REFRIGERANT • PT DATA v1
R-501
PT data, curve stats, and quick routes into the field calculators. Data shown here is derived from the versioned PT asset set under /assets/pt/v1.
At a glance
SAFETY • —
CURVE • bubble
POINTS • 442
GWP
ODP
Curves available
Dew + Bubble
Pressure range (psig)
-14.7 to 644.19
Temperature range (°F)
-241 to 200
Note: PT points are stored in psig and °F. For blends, bubble and dew represent different saturation states. Always follow OEM charging procedures.
Quick actions
These routes are designed to be technician-friendly: minimal taps, prefilled context, and predictable URLs for bookmarks and sharing.
Pressure → Saturation temperature (quick)
Linear interpolation between nearest points. Out-of-range values show “—”.
| Pressure (psig) | Sat Temp (°F) | Source |
|---|---|---|
| 0 | -41.2 | linear |
| 25 | 2 | linear |
| 50 | 27.1 | linear |
| 75 | 45.7 | linear |
| 100 | 60.7 | linear |
| 150 | 84.6 | linear |
| 200 | 103.7 | linear |
| 250 | 119.7 | linear |
| 300 | 133.6 | linear |
| 350 | 145.9 | linear |
| 400 | 157.1 | linear |
| 450 | 167.2 | linear |
Temperature → Saturation pressure (quick)
Useful for “I have a target saturation temp—what pressure should I see?” checks.
| Temp (°F) | Sat Pressure (psig) | Source |
|---|---|---|
| -40 | 0.4 | exact |
| -20 | 9.9 | exact |
| 0 | 23.4 | exact |
| 20 | 42 | exact |
| 40 | 66.7 | exact |
| 60 | 98.7 | exact |
| 80 | 139.2 | exact |
| 100 | 189.6 | exact |
| 120 | 251.1 | exact |
| 140 | 325.4 | exact |